ELECTRICAL RANGE

Home > Electrical Range

IBTC 2222 CONDUIT

Insulating, Bendable, Transversely Elastic, Corrugated Conduit System Non-flame propagating

designed for the protection of electrical installations, whether surface-mounted or concealed inside buildings.

The IBTC 2222 range is manufactured in accordance with Tunisian standards NT 87.169-1 (2010) and NT 87.169-22 (2007), and NT 87.169-22(2007) A11.

The IBTC 2222 range is distinguished by the blue string and yellow identification label found in each coil.

Laser marking on all coils allows us to determine 'when, on which machine, and by whom' a coil is manufactured. With this information, we can take quick and effective measures in case of any anomalies.

Packaging Table

Designation Ø Interior Ø Exterior Coil Length Draw Wire
D 16 IBTC 2222 Conduit 11 16 100 m Yes
D 20 IBTC 2222 Conduit 14 20 100 m Yes
D 25 IBTC 2222 Conduit 19 25 100 m Yes
D 32 IBTC 2222 Conduit 25 32 50 m Yes
D 40 IBTC 2222 Conduit 32 40 50 m Yes
D 50 IBTC 2222 Conduit 41 50 50 m Yes
  • Material : Polyolefins
  • Color : Gray
  • Equipped with a stainless-steel draw wire : The draw wire is made of galvanized steel 80/100° protected.
  • Non-flame propagating : 1Kw burner test
  • Shock resistance : 1 Joule at -5°C
  • Crush resistance: 320 N at 20 ±1°C
  • Insulation: ≥100Ω under a continuous voltage of 500 V
  • Heat resistance: Placement of the tube for 4 hours at a temperature of 60±2°C, then under a load of 2kg for 24 hours at the same temperature.
1st Digit 2nd Digit 3rd Digit 4th Digit
Crush Resistance Temperature Shock Resistance Min. Operating and Installation Max. Operating and Installation Temperature
1. 60°C
1. Very Light: 125 N 1. Very Light: 0,5j 1. +5°C 2. 90°C
2. Light: 320 N 2. Light: 1j 2. -5°C 3.105°C
3. Medium : 750 N 3. Medium: 2j 3. -15°C 4. 120°C
4. High : 1250 N 4. High: 6j 4. -25°C 5. 150°C
5. Very High :4000 N 5. Very High: 20j 5. -45°C 6. 250°C
7.400°C

Indeed, the ease of installation of IBTC 2222 tubes, attributed to the extremely light weight of the coil, bending radius, elasticity, and easy bending, combined with good crush and impact resistance, are significant advantages that result in substantial time savings in implementation, thus improving overall profitability. This reduction in installation time can reach up to 30%.

Furthermore, using the IBTC 2222 range in vertical installations or under ceilings provides significant cost savings due to its highly attractive price-to-quality ratio.

Number of wires to use per diameter
Ext. diameter Int. diameter Correspondence 1.5 2.5 4 6
16 11 9-11 3
20 14 11-13 4 3
25 19 16 5 4 2
32 25 21 6 5 3 2